⚡ Cable Size Calculator
BS7671 18th Edition • Full Correction Factors • Voltage Drop
Amendment 2:2022📋 Circuit Details
🔌 Cable Type
🌡️ Correction Factors
Combined Factor: 1.00
Required Iz = In ÷ factors = 32.00 A
📊 Results
Recommended Cable Size
2.5mm²
Twin & Earth (6242Y)
Current (It)
27 A
Required (Iz)
32 A
Voltage Drop
3.2%
VD (Volts)
7.4 V
✓ Current OK
✓ VD OK
| Parameter | Value | Limit | Status |
|---|
📝 Notes
| Size | It (A) | mV/A/m | VD % | Status |
|---|
📖 Quick Reference
Lighting1.0mm² / 6A
Ring Final2.5mm² / 32A
Radial 20A2.5mm² / 20A
Radial 32A4.0mm² / 32A
Cooker6-10mm² / 32-45A
Shower 8.5kW6.0mm² / 40A
Shower 10.5kW10mm² / 50A
EV 7kW6.0mm² / 32A
Lighting3% (6.9V)
Other5% (11.5V)
📉 Voltage Drop Calculator
Calculate VD for known cable size
📊 Result
Voltage Drop
0V
0% of supply
Status
-
mV/A/m
-
At Load
230 V
📊 Twin & Earth (6242Y) - Current Capacity
BS7671 Table 4D5
| mm² | Method A | Method B | Method C | mV/A/m |
|---|---|---|---|---|
| 1.0 | 11 | 13 | 15 | 44 |
| 1.5 | 14 | 16 | 19.5 | 29 |
| 2.5 | 18 | 22 | 27 | 18 |
| 4.0 | 24 | 30 | 37 | 11 |
| 6.0 | 31 | 38 | 47 | 7.3 |
| 10.0 | 42 | 52 | 65 | 4.4 |
| 16.0 | 56 | 69 | 87 | 2.8 |
| 25.0 | 73 | 90 | 114 | 1.75 |
🌡️ Temperature Factors (Ca)
| °C | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 70°C PVC | 1.03 | 1.00 | 0.94 | 0.87 | 0.79 | 0.71 |
📦 Grouping Factors (Cg)
| Circuits | 1 | 2 | 3 | 4 | 5 | 6 |
|---|---|---|---|---|---|---|
| Cg | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 |